Eaton 93PM UPS P-164000249
30-200 kW
User's and Installation Guide
Zobrazit stránku 0
1 2 3 4 5 6 ... 92 93

Shrnutí obsahu

Strany 1 - 30-200 kW

Eaton 93PM UPS P-16400024930-200 kWUser's and Installation Guide

Strany 2

2 30-200 kW P-164000249User's and Installation Guide Revision 2WARNING• The UPS is powered by its own energy source (batteries). The output termi

Strany 3 - Eaton 93PM UPS

P-164000249 30-200 kW 3Revision 2 User's and Installation GuideCAUTION• Installation or servicing should be performed by qualified service person

Strany 4

4 30-200 kW P-164000249User's and Installation Guide Revision 2• EMC Directive 2004/108/ECDeclaration of conformity with UPS harmonised standards

Strany 5 - Contents

P-164000249 30-200 kW 5Revision 2 User's and Installation GuideWARNINGHydrogen and oxygen gases are emitted from batteries into the surrounding a

Strany 6

6 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 1-2: WEEE symbolThis symbol indicates that you should not dis-card waste el

Strany 7 - List of Figures

P-164000249 30-200 kW 7Revision 2 User's and Installation Guide• Regional locations and telephone numbers• A question about any of the informatio

Strany 8 - List of Tables

8 30-200 kW P-164000249User's and Installation Guide Revision 22 Introduction to Eaton UPSThe Eaton® 93PM uninterruptible power supply (UPS) is a

Strany 9 - 1 Safety instructions

P-164000249 30-200 kW 9Revision 2 User's and Installation GuideFigure 2-1: Eaton 93PM UPS2.1 Looking inside the UPS systemThe system level static

Strany 10 - 2 30-200 kW P-164000249

10 30-200 kW P-164000249User's and Installation Guide Revision 2The 30-50 kW 93PM UPS includes a 50 kW rated static bypass section, one UPM power

Strany 11 - 1.2 CE marking

P-164000249 30-200 kW 11Revision 2 User's and Installation GuideFigure 2-2: 93PM 50 kW UPS wiring diagram

Strany 13 - P-164000249 30-200 kW 5

12 30-200 kW P-164000249User's and Installation Guide Revision 2In the 80-200 kW units, the UPM power modules are paralleled internally. These un

Strany 14 - 1.7 For more information

P-164000249 30-200 kW 13Revision 2 User's and Installation GuideThe rectifier input switch and battery breaker are available as standard for the

Strany 15 - P-164000249 30-200 kW 7

14 30-200 kW P-164000249User's and Installation Guide Revision 2Internal relay contactsFigure 2-4: Path of current through the UPS in double conv

Strany 16 - 2 Introduction to Eaton UPS

P-164000249 30-200 kW 15Revision 2 User's and Installation Guide2.2.1.2 Energy Saver System modeIn ESS mode the UPS safely provides mains current

Strany 17 - P-164000249 30-200 kW 9

16 30-200 kW P-164000249User's and Installation Guide Revision 2Internal relay contactsBattery breakerFigure 2-6: Path of current through the UPS

Strany 18 - 10 30-200 kW P-164000249

P-164000249 30-200 kW 17Revision 2 User's and Installation GuideNOTEThe critical load is not protected while the UPS is in Bypass mode.Internal r

Strany 19 - P-164000249 30-200 kW 11

18 30-200 kW P-164000249User's and Installation Guide Revision 22.3.1 Advanced Battery ManagementAdvanced Battery Management technology uses soph

Strany 20 - 12 30-200 kW P-164000249

P-164000249 30-200 kW 19Revision 2 User's and Installation Guide2.5 Options and accessoriesContact an Eaton sales representative for information

Strany 21 - 2.2 UPS operating modes

20 30-200 kW P-164000249User's and Installation Guide Revision 21. Maintenance Bypass Switch (MBP)2. Maintenance Isolation Switch (MIS)Figure 2-8

Strany 22 - Internal relay contacts

P-164000249 30-200 kW 21Revision 2 User's and Installation Guide1. Bypass Input Breaker (BIB)2. Maintenance Isolation Switch (MIS)3. Maintenance

Strany 23 - P-164000249 30-200 kW 15

Eaton 93PM UPS30-200 kWUser's and Installation Guide

Strany 24 - 2.2.3 Bypass mode

22 30-200 kW P-164000249User's and Installation Guide Revision 22.5.2 Top air exhaust kitThe top air exhaust kit is used to direct the UPS coolin

Strany 25 - 2.3 UPS features

P-164000249 30-200 kW 23Revision 2 User's and Installation Guide2.7 Basic system configurationsUPS power ratingThe maximum attainable UPS system

Strany 26 - 2.4.1 Customer interface

24 30-200 kW P-164000249User's and Installation Guide Revision 230-50 kW 80-100 kW 120-150 kW 160-200 kWRectifier input switch IS Standard Option

Strany 27 - 2.5 Options and accessories

P-164000249 30-200 kW 25Revision 2 User's and Installation Guide3 UPS installation plan and unpackingUse the following basic sequence of steps to

Strany 28 - 20 30-200 kW P-164000249

26 30-200 kW P-164000249User's and Installation Guide Revision 2Failure to follow guidelines may void your warranty.The UPS equipment operating e

Strany 29 - 1. Bypass Input Breaker (BIB)

P-164000249 30-200 kW 27Revision 2 User's and Installation Guide30-50 kW 80-200 kWFrom top of cabinet 500 mm 800 mmFrom front of cabinet 900 mm 9

Strany 30 - 2.6 Battery system

28 30-200 kW P-164000249User's and Installation Guide Revision 2Rating Heat rejection (BTU/h x 1000) Heat rejection (kW)30 kW 4.30 1.340 kW 5.73

Strany 31 - P-164000249 30-200 kW 23

P-164000249 30-200 kW 29Revision 2 User's and Installation GuideFigure 3-3: 93PM 160-200 kW UPS dimensionsFigure 3-4: Eaton 93PM 80-150 kW UPS To

Strany 32 - 24 30-200 kW P-164000249

30 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 3-5: Eaton 93PM 200 kW UPS Top air exhaust kit dimensions3.2.2 UPS system

Strany 33 - 3.2 Site preparations

P-164000249 30-200 kW 31Revision 2 User's and Installation Guide• The bypass feed into this equipment uses four wires. The rectifier feed into th

Strany 34 - 26 30-200 kW P-164000249

IMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manual contains important instructions that you should follow during installation and mainten

Strany 35 - P-164000249 30-200 kW 27

32 30-200 kW P-164000249User's and Installation Guide Revision 2RatedpowerRatedvoltageRectifierinputRatedcurrentRectifierinputMax.currentUPSOutpu

Strany 36 - 28 30-200 kW P-164000249

P-164000249 30-200 kW 33Revision 2 User's and Installation GuideTerminal function Terminal Function Tightening torque NmAC input to UPSrectifierX

Strany 37 - P-164000249 30-200 kW 29

34 30-200 kW P-164000249User's and Installation Guide Revision 23.2.3 UPS system interface wiring preparationControl wiring for features and opti

Strany 38 - 30 30-200 kW P-164000249

P-164000249 30-200 kW 35Revision 2 User's and Installation GuideNOTEThe UPS cabinet is heavy. If unpacking instructions are not closely followed,

Strany 39 - P-164000249 30-200 kW 31

36 30-200 kW P-164000249User's and Installation Guide Revision 24 UPS system installationThe customer has to supply the wiring to connect the UPS

Strany 40 - 32 30-200 kW P-164000249

P-164000249 30-200 kW 37Revision 2 User's and Installation Guide13. When all wiring is complete, reinstall safety shield panels removed in previo

Strany 41 - P-164000249 30-200 kW 33

38 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 4-2: 93PM 80-150 kW UPS gland plate and connector locations

Strany 42 - 34 30-200 kW P-164000249

P-164000249 30-200 kW 39Revision 2 User's and Installation GuideFigure 4-3: 93PM 160-200 kW UPS gland plate and connector locationsTop cable acce

Strany 43 - P-164000249 30-200 kW 35

40 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 4-4: 93PM 30-150 kW Top cable access kit4.2 Battery system installationThi

Strany 44 - 4 UPS system installation

P-164000249 30-200 kW 41Revision 2 User's and Installation Guide4.3 Installing UPS external battery cabinet and batterypower wiringFor the 93PM p

Strany 45 - P-164000249 30-200 kW 37

P-164000249 30-200 kW iRevision 2 User's and Installation GuideContents1 Safety instructions...

Strany 46 - 38 30-200 kW P-164000249

42 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 4-5: 93PM battery cabinet (EBC-S)

Strany 47 - Top cable access kit

P-164000249 30-200 kW 43Revision 2 User's and Installation GuideFigure 4-6: 93PM battery cabinet (EBC-L)

Strany 48 - 40 30-200 kW P-164000249

44 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 4-7: UPS cabinet through holesA DC-rated circuit breaker within each cabin

Strany 49 - P-164000249 30-200 kW 41

P-164000249 30-200 kW 45Revision 2 User's and Installation Guide8. If multiple cabinets are to be used, repeat the steps to the rest of the cabin

Strany 50 - 42 30-200 kW P-164000249

46 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 4-8: Connections of the EPO switchFrom remote EPO switch To customer inter

Strany 51 - P-164000249 30-200 kW 43

P-164000249 30-200 kW 47Revision 2 User's and Installation Guide4.5.2 Battery breaker wiring interfaceWhen using the original accessory battery c

Strany 52 - 44 30-200 kW P-164000249

48 30-200 kW P-164000249User's and Installation Guide Revision 24.6 Wiring parallel 93PM UPS systemsThe outputs of multiple 93PM UPS systems can

Strany 53 - P-164000249 30-200 kW 45

P-164000249 30-200 kW 49Revision 2 User's and Installation GuideMOB’sModule Output Breakers (MOBs) allow the output of the UPS to be disconnected

Strany 54 - 46 30-200 kW P-164000249

50 30-200 kW P-164000249User's and Installation Guide Revision 24.6.2 Control signals overviewTwo controls signals (External CAN Network, Bypass

Strany 55 - P-164000249 30-200 kW 47

P-164000249 30-200 kW 51Revision 2 User's and Installation GuideFigure 4-11: Simplified CAN and Pull-Chain wiring for parallel UPS systemNOTEThis

Strany 56 - 4.6.1 Power wiring overview

ii 30-200 kW P-164000249User's and Installation Guide Revision 26.1.1 Control panel...

Strany 57 - P-164000249 30-200 kW 49

52 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 4-13: CAN and Pull-Chain wiring for parallel UPS without MOBsNOTENC and NO

Strany 58 - 50 30-200 kW P-164000249

P-164000249 30-200 kW 53Revision 2 User's and Installation Guide5 Communication interfacesThis section describes the communication features of th

Strany 59 - P-164000249 30-200 kW 51

54 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 5-2: Network Card-MS• PX Gateway CardProvides remote monitoring through a

Strany 60 - 52 30-200 kW P-164000249

P-164000249 30-200 kW 55Revision 2 User's and Installation GuideFigure 5-4: Relay Card-MS• Network and MODBUS Card - MSProvides remote monitoring

Strany 61 - 5 Communication interfaces

56 30-200 kW P-164000249User's and Installation Guide Revision 2Figure 5-6: Industrial Relay Card-MS5.2 Intelligent Power SoftwareIntelligent Pow

Strany 62 - 54 30-200 kW P-164000249

P-164000249 30-200 kW 57Revision 2 User's and Installation GuideNOTEContacts should not be operated in excess of 30 VAC (RMS) and 30 VDC at 5 A m

Strany 63 - P-164000249 30-200 kW 55

58 30-200 kW P-164000249User's and Installation Guide Revision 26 UPS operating instructionsThis section describes how to operate the UPS.NOTEBef

Strany 64 - 5.3 Signal input monitoring

P-164000249 30-200 kW 59Revision 2 User's and Installation GuideFigure 6-1: Parts of the displayThe display consists of the following parts:• A:

Strany 65 - P-164000249 30-200 kW 57

60 30-200 kW P-164000249User's and Installation Guide Revision 26.1.2 Status indicatorsThe four symbols below the display are status indicators.

Strany 66 - 6 UPS operating instructions

P-164000249 30-200 kW 61Revision 2 User's and Installation Guide6.1.3 System eventsWhen the UPS system is running in Double conversion mode, it c

Strany 67 - P-164000249 30-200 kW 59

P-164000249 30-200 kW iiiRevision 2 User's and Installation GuideList of FiguresFigure 1-1: Recycling batteries symbol...

Strany 68 - 6.1.2 Status indicators

62 30-200 kW P-164000249User's and Installation Guide Revision 2Main menu Submenu FunctionsUPS module map Module map shows the statusof each UPM.

Strany 69 - 6.2 Steps to operate the UPS

P-164000249 30-200 kW 63Revision 2 User's and Installation Guide1.Press the lock button in the upper right corner of the screen.2. Type your pa

Strany 70 - 6.3 Signing in

64 30-200 kW P-164000249User's and Installation Guide Revision 26.4.2 Starting the UPS system in Bypass modeIf the inverter output of the UPS is

Strany 71 - STARTING

P-164000249 30-200 kW 65Revision 2 User's and Installation Guide6.4.4 Transfer from Bypass to Double conversion modeTo transfer the critical load

Strany 72 - 64 30-200 kW P-164000249

66 30-200 kW P-164000249User's and Installation Guide Revision 26.4.7 UPS system and critical load shutdownTo perform maintenance or service on t

Strany 73 - P-164000249 30-200 kW 65

P-164000249 30-200 kW 67Revision 2 User's and Installation Guide3.To restart the UPS system, follow the procedure in Chapter 6.4.1 Starting the U

Strany 74 - 66 30-200 kW P-164000249

68 30-200 kW P-164000249User's and Installation Guide Revision 26.5.3 Enabling and disabling the battery chargerTo turn the battery charger on or

Strany 75 - 6.5 UPS control instructions

P-164000249 30-200 kW 69Revision 2 User's and Installation Guide4. On the UPM control screen, select Shut down module.6.7 Using the Remote Emerge

Strany 76 - 6.6 UPM control instructions

70 30-200 kW P-164000249User's and Installation Guide Revision 2NOTEThe integral MBS and Static Bypass need to supplied by the same source.To tur

Strany 77 - P-164000249 30-200 kW 69

P-164000249 30-200 kW 71Revision 2 User's and Installation Guide6.9 Turning UPS from mechanical bypass to doubleconversion modeTo turn the UPS ba

Strany 78 - Switch (MBS)

iv 30-200 kW P-164000249User's and Installation Guide Revision 2List of TablesTable 2-1: UPS configurations...

Strany 79 - P-164000249 30-200 kW 71

72 30-200 kW P-164000249User's and Installation Guide Revision 27 UPS maintenanceThe components inside the UPS cabinet are secured to a sturdy me

Strany 80 - 7 UPS maintenance

P-164000249 30-200 kW 73Revision 2 User's and Installation Guide7.2 Performing preventive maintenanceThe UPS system requires very little preventi

Strany 81 - 7.2.3 PERIODIC maintenance

74 30-200 kW P-164000249User's and Installation Guide Revision 2NOTEWork on energized circuit must be performed only by authorized personnel.7.2.

Strany 82 - 7.2.5 BATTERY maintenance

P-164000249 30-200 kW 75Revision 2 User's and Installation GuideDANGERHAZARDOUS MATERIALS. Batteries may contain HIGH VOLTAGES, and CAUSTIC, TOXI

Strany 83 - 7.4 Maintenance training

76 30-200 kW P-164000249User's and Installation Guide Revision 28 Technical dataFor complete technical specification, contact your Eaton represen

Strany 84 - 8 Technical data

P-164000249 30-200 kW 77Revision 2 User's and Installation Guide8.2 UPS system inputRated input voltageVoltage tolerance, (Rectifier input)Voltag

Strany 85 - 8.3 UPS system output

78 30-200 kW P-164000249User's and Installation Guide Revision 2Total voltage harmonic distortion100 % linear load100 % non-linear load< 1 %&l

Strany 86 - 8.4 Battery specification

P-164000249 30-200 kW 79Revision 2 User's and Installation GuideBattery quantity 30-50 kW units: 36 blocks, 216 cells per battery string80-200 kW

Strany 87 - P-164000249 30-200 kW 79

80 30-200 kW P-164000249User's and Installation Guide Revision 2Ambient service temperature range, (UPS) From +5 °C to +40 °C*No output power der

Strany 88 - 80 30-200 kW P-164000249

P-164000249 30-200 kW 81Revision 2 User's and Installation Guide9 WarrantyThe product is warranted against defects in materials and workmanship f

Strany 89 - 9 Warranty

P-164000249 30-200 kW 1Revision 2 User's and Installation Guide1 Safety instructionsIMPORTANT SAFETY INSTRUCTIONSSAVE THESE INSTRUCTIONSThis manu

Strany 90 - 10 Installation checklist

82 30-200 kW P-164000249User's and Installation Guide Revision 210 Installation checklistAll packing materials and restraints have been removed f

Strany 91 - P-164000249 30-200 kW 83

P-164000249 30-200 kW 83Revision 2 User's and Installation GuideJumper is installed on EPO between pins 1 and 2 if EPO is used in the NC configur

Strany 92 - 11 APPENDIX A: User settings

84 30-200 kW P-164000249User's and Installation Guide Revision 211 APPENDIX A: User settingsThe UPS has the following settings that are user modi

Strany 93 - Table 11-2: Config settings

P-164000249 30-200 kW 85Revision 2 User's and Installation GuideSetting DescriptionConfig P/W level 2 Change the level 2 password. The default va