www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card – User Manual 34003991XT_EN/EG Page 107/142
#> getShutdown 1 ShutdownDuration
6.4.5.2 “setShutdown”
To modify a shutdown setting
setShutdown N [option1] [option2] ...
N = 1|2|3
options for N=1:
iName = “xx..xx”
RunTimeToEmptyLimit = xx (0..9999 in sec)
RemainingCapacityLimit = xx (0..100 in sec)
ShutdownTimerSelected = 0|1 (0=No, 1=Yes)
ShutdownTimer = xx (0..5999940/60 in min)
ShutdownDuration = xx (0..999 in sec)
RestartLevel = xx (0..100 %)
options for N=2 or 3:
iName = “xx..xx”
ShutdownTimer = xx (99..99999 in sec)
RemainingCapacityLimit = xx (0..100 in sec)
ShutdownDuration = xx (0..999 in sec)
StartupTimer = xx (0..65535 in sec)
#> setShutdown 1 ShutdownDuration=120
6.4.6 Access control settings
6.4.6.1 “getAccess”
To read an access control setting
getAccess [option1] [option2]...
options :
Login
Password
(1)
Security
(1)
: All characters are replaced with the star character ‘*’
6.4.6.2 “setAccess”
To modify an access control setting
setAccess [option1] [option2]