www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card – User Manual 34003991XT_EN/EG Page 114/142
6.4.9.3 “getTemp”
To read a temperature setting
getTemp [option1] [option2] ...
options :
Unit
HighThreshold
LowThreshold
Hysteresis
Offset
HighNotify
LowNotify
HighShutdown
LowShutdown
6.4.9.4 “setTemp”
To modify a temperature setting
setTemp [option1] [option2] ...
options :
Unit = C|K
HighThreshold = xx
LowThreshold = xx
Hysteresis = xx (0..5)
Offset = xx (-5..5)
HighNotify = 0|1 (0=No, 1=Yes)
LowNotify = 0|1 (0=No, 1=Yes)
HighShutdown = 0|1 (0=No, 1=Yes)
(1)
LowShutdown = 0|1 (0=No, 1=Yes)
(1)
(1)
: Writing enabled only if the notification is enabled
6.4.9.5 “getHum”
To read a humidity setting
getHum [option1] [option2] ...
options :
HighThreshold
LowThreshold
Hysteresis
Offset