4.2.1.3 Viewing the modules (Only with Eaton MX Frame UPS)
Click on UPS Modules scroll list to view the information about the UPS modules.
Active sources:
x UPS + y UPS redundant : x indicates the minimal number of UPS necessary to power the load,
y indicates the number of UPS in redundancy.
The addition of these 2 values is the total number of available UPS.
The Minimum redundant UPS modules to trigger alarm can be configured from this page. The button
Save makes the card setting the parameter into the UPS. A warning message informs the user about the
consequences of this parameters modification.
The redundancy lost can generate Email notification (if set in the email notification page) and SNMP
trap. It can also be used by IPP for server protection criteria.
The Module Nr gives the location of the module in the UPS.