Network Management Card User Manual 34003991XT_EN/EG Page 14/142
in/out
TCP
5000
in/out
UDP
4679, 4680R
out
UDP
1812*
out
TCP
389*
* These ports can be changed by the user, the values shown are the defaults defined by the standards.
1.3.6 Environment sensor
Temperature measurement from 0 to 70 °C with +/- 1 °C accuracy.
Measurement of humidity from 0 to 100 % with +/- 6 % accuracy.
Min / max time-stamped function for temperature and humidity.
Choice of temperature readings in Celsius or Fahrenheit.
High and low thresholds, hysteresis and offset adjustable via Web interface.
Possibility of notification of status changes by e-mail, SMS or SNMP trap.
SMS notification requires the use of a third-party application that converts emails to SMS.
Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m).
Name and status of each configurable contact.
Recording of events and measurements in the card log
Possibility of shutting down the installation in the event of a threshold being exceeded or on opening /
closure of a dry contact
Connection to the card with straight shielded CAT5 RJ45 network cables (maximum card/sensor
distance: 10 m)
1.3.7 MIB (Management Information Base)
The card is Compatible with following MIBs:
MIB II (RFC 1213)
Internet Engineering Task Force (IETF) Standard UPS MIB (RFC 1628)
EATON Pulsar MIB (ex MGE) V1.7
EATON Powerware MIB (PowerMib)
See the appendix Chapter