Eaton Network Management Card Uživatelský manuál Strana 76

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 142
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 75
www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card User Manual 34003991XT_EN/EG Page 76/142
Start of the shutdown sequence
Delay before
shutdown
Utility failure
Remaining autonomy
100%
Shutdown after :
If remaining time under
UPS Shut off
Card parameters
UPS parameters
Shutdown duration
Battery
capacity
0%
Shutdown if
remainig
capacity under
t
5.1.1.1 Backup time before initiating the shutdown procedure
(Shutdown After Shutdown Timer)
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and
launches the system shutdown procedure at the end of the countdown.
This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding
battery backup time.
Note 1:
The Intelligent Power Protector can also manage its own Shutdown Timer (configurable in the Shutdown
Module"set-up" menu of each Intelligent Power Protector) launched when the UPS switches to battery.
Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored
is not guaranteed (e.g. power restoration if only this system was shut down).
5.1.1.2 Initiating the shutdown procedure when the battery level is lower than:
(If Capacity under)
When the card detects that the remaining backup time percentage is less than the configured level, the shutdown
sequence is started.
By default, this value is set at 20%.
Note:
The UPS already manages an equivalent parameter for the end of backup pre-alarm.
Zobrazit stránku 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 141 142

Komentáře k této Příručce

Žádné komentáře