Network Management Card User Manual 34003991XT_EN/EG Page 134/142
upsEnvironmentHumidityOK
Trap 60
Level 2
upsEnvironmentInput1Closed
Trap 61
Level 2
upsEnvironmentInput1Open
Trap 62
Level 2
upsEnvironmentInput2Open
Trap 64
Level 2
upsEnvironmentInput2Closed
Trap 63
Level 2
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified
applications” page
8.2.4 EATON Powerware MIB
The Card implements the full Eaton Powerware MIB (PowerMIB), including alarm tables. The Eaton traps are
sent. The Eaton Powerware MIB access path is 1.3.6.1.4.1.534.
Table is an abbreviated list of objects from the PowerMIB. The UPS output/load segment controls objects and the
entire MIB description is available at http://powerquality.eaton.com/Support/SoftwareDrivers.
MIB Object
SNMP Format
Add.path
xupsIdentManufacturer
String
{1.1.0}
xupsIdentModel
String
{1.2.0}
xupsIdentSoftwareVersion
String
{1.3.0}
xupsIdentOemCode
Integer
{1.4.0}
xupsBatTimeRemaining
Seconds
{2.1.0}
xupsBatVoltage
Volts DC
{2.2.0}
xupsBatCurrent
Amps DC
{2.3.0}
xupsBatCapacity
Percent
{2.4.0}
xupsBatteryAbmStatus
Integer
{2.5.0}
xupsBatteryLastReplacedDate
String
{2.6.0}
xupsInputFrequency
0.1 Hertz
{3.1.0}
xupsInputLineBads
Integer
{3.2.0}
xupsInputNumPhases
Integer
{3.3.0}
xupsInputTable
{3.4.0}
xupsInputPhase
Integer
{3.4.1.1.x}
xupsInputVoltage
RMS Volts
{3.4.1.2.x}
xupsInputCurrent
RMS Amps
{3.4.1.3.x}
xupsInputWatts
Watts
{3.4.1.4.x}
xupsInputSource
Integer
{3.5.0}
xupsDualInputStatus
Integer
{3.6.0}