User Manual
Network Management Card User Manual 34003991XT_EN/EG Page 81/142
Shutdown duration
Start shutdown main
output
Utility failure
Utility
Battery capacity
under:
NSM 2 on output 1
NSM 1 on main
output
Main output
Utility restore
Start shutdown
output 1
Output 1
Shutdown
duration output 1
Battery capacity
under: (output 1)
5.2.3 Case of power restoration before the end of the "shutdown duration" counter
If power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration for
a time equal to the forced reboot delay (10 seconds)
Shutdown
duration
Forced Reboot
Start shutdown main
output
Utility failure
Utility
Battery capacity under
:
NSM 2 on output 1
NSM 1 on main
output
Main output
Utility restore
Start shutdown
output 1
Output 1
Shutdown
duration output 1
Battery capacity
under: (output 1)